User manual

User Manual Page 69 of 74
(PVI-6000-OUTD-UK-W Rev.1.0)
8 TECHNICAL FEATURES
8.1 Input Values
WARNING: The output voltage from the rectifier shall always be less than
600VDC.
WARNING: Inverter is provided with a linear output power derating
depending on the input voltage, starting from 530 Vdc (100% output power)
to 580 Vdc (0% output power)
Description
Value
PVI – 6000-OUTD-UK-W
Max. absolute input voltage 600 Vdc
Input voltage, MPPT operating
range
from 50 Vdc to 580 Vdc
Input voltage, MPPT operating
range at full power
from 180 Vdc to 530 Vdc
Max. short circuit current. 44 Adc
Max. operating input current 36 Adc
Max. input power 8,000 W
Generator Ground fault
protection
Ground fault detector provided