User Guide

Table Of Contents
Single Zone Gas Monitor
4 P/N: 3015-4256 Rev 10
Figure 1-1. Aerial View of Example Single Zone Leak Monitor Placement in a Mechanical Room
1.7. Specifications
Category HGM-SZ Specifications
Product Type
Single-zone infrared monitoring system for low level continuous monitoring of CFC, HCFC
and HFC refrigerant gasses used in most commercial refrigeration systems. System design
supports compliance to the refrigerant monitoring requirements of ANSI/BSR ASHRAE 15-
2007 and ASHRAE Safety Code 34-2007.
Gas Library:
CFC
HFP, R-11, R-113, R-114, R-12, R-502
HFC
R-125, R-134a, R-236FA, R-245Fa, R-404a (HP62), R-407a, R-407c (AC9000), R-410a
(AZ20), R-422a, R-422d, R-427a, R-507 (AZ50), R-508b (SUVA95)
HCFC
R-123, R-124, R-21, R-22, R-227, R-23, R-401a (MP39), R-402a (HP80), R-402b (HP81),
R-408a, R-409a, R-500, R-503
HALON
H1211, H1301, H2402
Other
FA188, FC72, HFO1234YF, N1230, R-420a, R-424a, R-426a, R-427a, R-438a
Sensitivity
All gasses 1 ppm
Measuring
Range
All gasses 0 to 10,000 ppm
Accuracy
±1 ppm ±10% of reading from 0-1000 ppm
(R11, R22, R113: ±10 ppm ±15% of reading 0-1000 ppm)
Response Time
105 seconds maximum (dependent on sample line length)