Specifications

Halogen Gas Monitor – MultiZone Remote Display
Instruction 3015-5157 26
Refrigerant
This is the type of refrigerant gas being monitored.
1. Press the ENTER key to adjust the setting.
2. Use the UP/DOWN cursor keys to scroll through the list of gas types.
3. Press ENTER to accept the entry or ESC to revert to the previous setting.
Distance
This is the tubing length in feet from the HGM-MZ to the termination of the air intake line. This value may
range from 0 to 500 feet. The default value is 100 feet. Setting this value to “0” causes the zone to be
bypassed during normal operation, and the word “DISABLED” to appear in place of the zone’s PPM reading
in the Zone Screen.
1. Press the ENTER key to modify the number.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or ESC to revert to the previous setting.
Average Temperature
This temperature reading may be changed to the exact temperature at the sample point for greater accuracy.
The adjustment range is from –50 to +70 degrees C.
1. Press the ENTER key to adjust the temperature value.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the setting.
3. Press ENTER to accept the new entry or ESC to revert to the previous setting.
Current PPM
This box displays the last PPM measurement recorded in this zone. You can not modify this value.
Log Interval
Sets the length of time between entries in the trend log. The default is one entry every 1440 minutes (24 hrs).
A value of 000 indicates that each measurement for a given zone is logged into the trend log.
1. Press the ENTER key to adjust the log interval value.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the setting.
3. Press ENTER to accept the new entry or ESC to revert to the previous setting.