Specifications

Halogen Gas Monitor – MultiZone Remote Display
Instruction 3015-5157 27
Navigating to the 2
nd
Zone Setup Screen
On Zone Setup Screen #1, select MORE to access Zone Setup Screen #2. Select BACK to return to Zone
Setup Screen #1. To return to the System Screen, press ESC.
Zone Setup Screen #1 Zone Setup Screen #2
Leak Level
This is the concentration level in PPM that will activate a leak alarm condition.
1. Press the ENTER key to adjust the value.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or ESC to revert to the previous setting.
NOTE: This value must be less than the spill level.
Spill Level
This is the concentration level in PPM that will activate a spill alarm condition.
1. Press the ENTER key to adjust the value.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or ESC to revert to the previous setting.
NOTE: This value must be less than the evacuate level and greater than the leak level.
Evacuation Level
This is the concentration level in PPM that will activate an evacuate alarm condition.
1. Press the ENTER key to adjust the value.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or ESC to revert to the previous setting.
NOTE: This value must be greater than the spill level.
Re-Setting the Peak PPM Value
Pressing this key resets the current peak PPM level stored in memory and displays it at the top of the screen.