Datasheet

203
Technical characteristics
MINI CAM SWITCHES
>
Characteristics
Data
>
Thermal current Ith
10 A
>
Rated operating current Ie
-inAC21 10A
-inAC15
2.5 A
>
Motor performance in AC-3
-3x230V
1.8 kW
-3x400V
2.2 kW
>
Motor performance in AC-23
-1x230V
0.75 kW
-1x400V
1.1 kW
-3x230V
1.8 kW
-3x400V
3kW
>
Rated insulation voltage Ui(V)
500 V
>
Rated operating current in DC-1
L/R < 1ms
-24VDC
10 A
-40VDC
6A
-60VDC
2.5 A
- 110 V DC
0.7 A
-220VDC
0.3 A
>
Rated conditional short-circuit current
3kA
>
Max. fuse rating
10 A
>
Degree of protection
IP 65
IP 2x
at the rear of the panel
>
Wire size (flexible and rigid)
2 x 1.5
mm
2
max.
1x0.5
mm
2
min.
>
Operating temperature
-20°C
to
+50°C
>
Standards
IEC 60947-1
IEC 60947-3
CSA 22.2
UL 508
CAM SWITCHES
>
Characteristics
PR 12 PR 17 PR 21 PR 26 PR 40 PR 63 PR 125 PR 160
>
For thermal current Ith Ic(A)
20 25 32 40 63 63 200 250
>
Rated operating current for AC-21 A Ie(A)
(IEC 60 947-3)
Switching of resistive loads
including moderate overloads
16 20 25 32 50 63 160 200
>
Rated operating current for AC-15 A Ie(A) at 230V AC
(IEC 60 947-3)
Control of
electromagnetic loads
6 8 10 12
-- - -