Datasheet

95
Technical characteristics
Screw and plug-in connection characteristics
Standards
Data
>
Rated insulation voltage
690 V
AC
IEC 60947-1
600 V
AC
UL 508
>
NC contacts Positive opening
IEC 60947-5-1
>
Rated impulse voltage Uimp 6kV
Pollution degree 3
>
Conventional thermal current in free air conditions
AC15: 10 A IEC 60947-5-1
DC13: 2,5 A
>
Electrical ratings Alternating current Direct current
IEC 60947-5-1
AC15 - A 600 DC13 - Q 600
Ue = 120 V, Ie = 6 A Ue = 125 V, Ie = 0,55 A
Ue = 24 0 V, Ie = 3 A Ue = 2 50 V, I e = 0, 27 A
Ue = 380 V, Ie = 1,9 A Ue = 400 V, Ie = 0,15 A
Ue=480V,Ie=1,5A Ue=500V,Ie=0,13A
Ue = 500 V, Ie = 1,4 A Ue = 600 V, Ie = 0,1 A
Ue = 600 V, Ie = 1,2 A
Minimum operating current
- standard blocks - golden contacts
Ue = 24 V DC and Ie = 5 mA Ue = 5 V DC and Ie = 1 mA
Failure rate < 10
-8
Failure rate < 10
-8
>
Electrical operating life 1 million cycles for:
- AC15 - B 300 - DC13 - R 300
Ue = 120 V, Ie = 3 A Ue = 125 V, Ie = 0,22 A
Ue = 240 V, Ie = 1,5 A Ue = 250 V, Ie = 0,1 A
>
Applicable wire sizes Rigid or flexible wire without ferrule:
0,5
mm
2
to
2x2,5
mm
2
Rigid or flexible wire with ferrule:
0,5
mm
2
to
2 x 1,5
mm
2
CONTACT BLOCKS
>
Faston connection
Standards
Data
>
Rated insulation voltage
320 V
AC
IEC 60947-1
300 V
AC
UL 508
>
NC contacts Positive opening
IEC 60947-5-1
>
Rated impulse withstanding voltage Uimp 6 kV
Pollution degree 3
>
Conventional thermal current in free air conditions
AC15:10A IEC60947-5-1
DC 13: 2,5 A
>
Electrical ratings Alternating current Direct current
IEC 60947-5-1
AC15 - A 300 DC13 - Q 300
Ue = 120 V, Ie = 6 A Ue = 125 V, Ie = 0,55 A
Ue = 24 0 V, Ie = 3 A Ue = 2 50 V, I e = 0, 27 A
Minimum current of use
Ue = 24 V DC and Ie = 5 mA
Failure ra
te < 10
-8
>
Electrical opera
ting life
1 million cycles for:
- AC15 - B 300 - DC13 - R 300
Ue = 120 V, Ie = 3 A Ue = 125 V, Ie = 0,22 A
Ue = 240
V,Ie=1,5A Ue=250V,Ie=0,1A
>
Faston size 6,35 mm or 2 x 2,8 mm