Specifications

HBZTX6-IN-4 Page 13
6.4 Alarm Input Connections
The ZTX6 has the same number of alarm inputs as camera inputs (they are not dedicated to
the corresponding camera input). On each module they are numbered on the graphic from 1
to 8 (see Figure 5 on page 17). They are actually numbered in the same way as the
cameras, the base unit (ZTX6/8M2) contains inputs 1 to 8, the first additional module
(ZTX6/MOD) contains inputs 9 to 16 (but labelled 1 to 8), the second 17 to 24 and the third
25 to 32 (see Figure 5).
Electrically the alarms operate from volts-free relay closures (or openings) and the inputs
can be individually configured in the on-screen menus to respond to normally-open or
normally-closed contacts.
Remove the 5-way terminal block
Connect from each terminal to your alarm relays (see Figure 2)
Group the returns and lead them into the common connection
The alarm-input connections are normally-open as a default. If you are connecting normally-
closed alarms do not connect your alarm terminal-blocks yet wait until you have changed the
alarm configuration in the on-screen menus.
Figure 2. Alarm Input Connections
6.5 Alarm Output Connections
The base unit has 2 alarm output contacts as shown below. Each alarm input on your ZTX6
can be set to trigger one or the other, both or neither in the on-screen menus. The output
relays can be set to normally-open or normally-closed individually in the on-screen menus.
They are normally-open as a default.
CAUTION: Normally-closed alarm-output-relays are reliant on a power-supply.
When the unit is switched off they immediately revert to the open state.
The relays switch a maximum of 30V, 2A each.
Figure 3. Alarm Output Relay Connections
Wire your alarm output devices according to Figure 3.
C
is the common
or return connection
1
5
2
6
3
7
4
8
C
C
12
relay 2relay 1