Technical data

Technical Data
120-393 632.4 04.08 Fh
PARAMOUNT two 30 - 115 kW 15
3.5 Sensor value tables
Table 4: Resistance values for outside temperature sensor ATF
Temperature [°C]
Resistance [Ω]
-20 8194
-15 6256
-10 4825
-5 3758
0 2954
5 2342
10 1872
15 1508
20 1224
25 1000
30 823
Table 5: Resistance values for flow sensor, DHW sensor, return sensor,
sensor B4
Temperature [°C]
Resistance [Ω]
0 32555
5 25339
10 19873
15 15699
20 12488
25 10000
30 8059
35 6535
40 5330
45 4372
50 3605
55 2989
60 2490
65 2084
70 1753
75 1481
80 1256
85 1070
90 915
95 786
100 677