Technical data

Installation
24 POTTERTON COMMERCIAL
120-393 632.4 04.08 Fh
5.7 Gas connection
The connection of the gas must only be carried out by an approved
gas installation specialist. The setting data of the manufacturer on
the device and additional requirements have to be checked with
the local supply conditions for the gas installation and setting.
Residues in pipes and pipe joints should be removed.
Check tightness
The entire gas inlet pipe, particularly the joints must be checked
for leakages before commissioning.
The gas burner valve on the gas burner must only be pressure- tes-
ted at maximum 150 mbar.
De-air gas pipe
The gas pipe has to be de-aired before commissioning.
Factory settings
The PARAMOUNT two has been set at nominal heat load by the ma-
nufacturer.
The gas type can be seen on the glued on additional plate on the
boiler. The data, set by the manufacturer, has to be checked with
the local supply conditions before instalation of the PARAMOUNT
two. The gas pressure controller of the gas valve has been sealed.
Supply Pressure
The supply pressure must lie between the following values:
For natural gas
: 17 mbar - 25 mbar
For LPG
: nominal 37 mbar
The connecting pressure is measured as pressure in the gas flow at
the measuring nozzle of the gas valve (fig. 5 and fig. 6).
E Below eaves 200 500
F Below Balcony or car port roof 200 500
G From a vertical drain pipe or soil pipe 150 150
H
From an internal or an external comer or to a
boundary alongside the terminal
300 600
I Above ground, roof or balcony level 300(1) 600 (1) (2)
J From a surface or a boundary facing the terminal 600 1000
K From a terminal facing a terminal 1200 2000
L From an opening in the car port into the building 1200 2000
M Vertically from an terminal on the same wall (3) 1500 1500
N Horizontally from a terminal on the same wall (3) 300 600
P From a structure on the roof 600 1000
Q
Above the highest point of intersection with the roof,
with a pitch less than 45°
600 1000
Q
Above the highest point of intersection with the roof,
with a pitch less than 45°
1000 1000
All measurements are in mm.
1. For terminals below 2 meters from ground level a suitable guard must be fitted.
2. The height to the centre line of the flue terminal shall not be less than 2 meters from occupied external areas.
3. Groups of appliances of 150 kW total heat input need to comply with the clean air Act with respect to discharge at high level.
Location PARAMOUNT two 30/40/60
PARAMOUNT two 80/95/
115