Technical data

Installation
120-393 632.4 04.08 Fh
PARAMOUNT two 30 - 115 kW 27
Adjusting and Checking the CO2 values
Operate the PARAMOUNT two in the controller stop mode to adjust
and
check the CO2 value.
Controller Stop Mode (manual adjustment of burner load)
Press operation mode button Heating Operation for approxima-
tely 3 seconds, until the message Regulator Stop Function ON is
displayed.
Wait, until the display has reached the basic display again.
Press information button. The message Regulator Stop, set No-
minal Value appears in the display. The actual modulation de-
gree will be displayed on the display.
Press OK-button. The nominal value can now be changed and
must, afterwards, to be acknowledged with the OK-button. In
this way, the displayed nominal value is taken over by the con-
trol.
The regulator stop function is stopped by pressing the operating
mode button Heating Operation for approximately 3 seconds, rea-
ching the maximum boiler temperature or a time limit.
Fig. 7: Gas valve