Technical data

Programming
120-393 632.4 04.08 Fh
PARAMOUNT two 30 - 115 kW 53
If the colder storage temperature rises above the legionella func-
tion setpoint -1 K, the legionella function setpoint is assumed as
met and the timer starts running. If the storage temperature drops
by more than the switching difference +2 K below the required le-
gionella function setpoint, the duration has to be met again. If no
duration has been set, the legionella funtion has been met imme-
diately on reaching the legionella function setpoint.
Circulating pump release
(1660)
Time program 3: The circulation pump is released, depending on
the time program 3 (see prog. no. 540 to 556).
DHW release: The circulation pump will be released, when the
DHW preparation has been released.
Time program 4/DHW: The circulation pump will be released, de-
pending on the time program 4 of the local controller.
Circulation pump cycle
operation
(1661)
The circulation pump will be switched on for 10 minutes and off for
20 minutes within the release time.
Boiler
Setpoint manual control
(2214)
Temperature, to which the boiler will be contolled in manual con-
trol mode (also see prog. no. 7140).
DHW storage tank
Flow setpoint boost
(5020)
The boiler temperature setpoint for charging the DHW storage tank
consists of the DHW temperature setpoint and the flow setpoint
boost.
Configuration
Hydraulic diagram
(5701)
Setting of the code for the hydraulic system. The data of the codes
are included in the respective instructions of the accessories.
Heating circuit 1/2
(5710 ad 5715)
With this parameter the heating circuits can be deactivated.
This adjustment directly affects the heating circuits and has no in-
fluence on the operating unit!
System pump
(5761)
The system pump can be used to support the heating circuits and
the DHW circuit. Under prog. no. 5761 it is specified, which kind of
heat request will be supported by the system pump. The following
kinds of heat requests are available:
Zones with system pump
HC1 with system pump
HC2 with system pump
DHW with system pump
Relay outputs
(5920 to 5928)
Default: Function according to hydraulic diagram.
Status output: The status output will be operated when a com-
mand exists from the controller to the firing automation. If there
is a fault, which prevents the firing automation to operate, the sta-
tus output will be switched off.
Alarm output: The output will be set, when there is a fault in the
device, which requires manual unlocking.
Status information: The output is set, when the burner operates.