Technical data

Programming
120-393 632.4 04.08 Fh
PARAMOUNT two 30 - 115 kW 57
sensor is connected at the input, which must be installed in the
flow behind the hydraulic bypass.
Check sign flue gas damper: See prog. no. 5920 and 5950.
Heat generation lock: See prog. no. 5950.
Heat generation lock inverse: See prog. no. 5950.
Heat generation lock sensor: If there is a temperature at the sen-
sor which is higher than the actually requested nominal value, the
boiler will be locked. The control of the heating circuits and the
utility water stays activated.
External maximum
nominal flow value
(5975)
See prog no. 5973.
External capacity
process threshold
(5976)
See prog no. 5973.
Time constant building
(6110)
The reaction speed of the nominal flow value at fluctuating outside
temperatures is influenced by the value set here, depending on the
building design.
Example values:
40 for buildings with thick walls or outer insulation.
20 for buildings of normal building design.
10 for buildings of light building design.
Bit-settings
Only the listed settings may be changed. Record every change!
All other bit settings must not be changed!
ConfigRG1
(6240)
Priority DHW RG1.0 = 0 and
RG1.1 = 0: Absolute priority
RG1.0 = 0 and
RG1.1 = 1: No priority
RG1.0 = 1 and
RG1.1 = 0: Shifting
System Frost Protection RG1.4 = 0: Frost protection OFF
RG1.4 = 1: Frost protection ON
Operation mode of the
heating circuit at activat-
ed modem function
RG1.7 = 0: Standby operation
RG1.7 = 1: Reduced mode operation
LPB
Device address
(6600)
The actual LPB device address will be displayed.
Fault
If the sign appears in the display, a fault exists and the respec-
tive fault message can be called up via the information button
SW Diagnosics code
(6705)
In case of a disturbance, the display Disturbance is on permanent-
ly. In addition, the diagnosis code is issued via the display (see
chapter Maintenance, fault code table).
Burner ctrl phase lock-
out pos
Phase, in which the fault occured, which led to the disturbance.