Technical data

Programming
58 POTTERTON COMMERCIAL
120-393 632.4 04.08 Fh
Maintenance / Service
Message
(7001)
Messages to signal necessary maintenance work. The following
causes may be the reason for the occurance of a maintenance mes-
sage:
Burner operating hours interval time exceeded since the last
maintenance work
Start-up interval time exceeded since the last maintenance
Number of month exceeded since the last maintenance
Ionisation current maintenance threshold undercut
After the appearance of a maintenance message, the heating spe-
cialist has to be informed. If necessary, the heating specialist can
instruct the end user to call up the maintenance code, so that the
maintenance cause can be found. In this way, preparations can be
made to carry out servicing, if necessary.
Acknowledge
ment
message
(7010)
The end user has the opportunity to acknowledge on end user level
the displayed maintenance message by editing parameters. After
this, the message is cancelled in the whole system.
Reset messages
(7012)
Manual control
(7140)
Activation of manual control. If the manual control function is ac-
tivated the boiler will be controlled to the Setpoint manual cont-
rol. All pumps will be activated. Additional request will be ignored!
State
State
(8000 to 8007)
With this function the state of the selected system can be reques-
ted.
The following messages are possible under Heating circuit 1/2:
The following messages are possible under DHW:
Reset messages 1 1 = Individual reset of operation hours maintenance message
Reset messages 2 1 = Individual reset of start-up maintenance message
Reset messages 3 1 = Individual reset of the months-service-maintenance message
Reset messages 4 1 = Individual reset of ionisation current maintenance message
Reset messages 6 1 = Total reset of all maintenance messages
Display Dependend on
--- No heating circuit available
Manual control active Manual control active
Floor curing function active Floor curing function active
Opt start ctrl+boost heating
Optimum start control
Boost heating
Comfort heating mode Time switching program, operating mode, occupancy button
Optimum stop control
Reduced heating mode
Time switching program, holiday program, operating mode, occu-
pancy button, H1
Frost prot room active Holiday program, operating mode, H1
Summer operation
24-hour Eco active
Setback reduced
Time switching program, holiday program, operating mode, occu-
pancy button, H1
Setback frost protection Holiday program, operating mode, H1
Room temp limitation
Display Dependend on
--- Not available
Manual control active Manual control active