Technical data

Servicing
120-393 632.4 04.08 Fh
PARAMOUNT two 30 - 115 kW 63
10.4 Removing gas burner
The gas burner has to be dismantled before cleaning the heating
surfaces.
Dismantling of the gas burner (PARAMOUNT two 30/40)
Disconnect the connecting wires to the fan.
Disconnect ionisation cable.
Disconnect ignition cable.
Remove fastening screws of the bracket on the housing lid.
Remove the screw connections of the gas connection pipe at the
mixing chamber and the gas valve.
Remove the gas connection pipe and the gas injector.
Disconnect the gas connection pipe at the gas valve and remove
gas valve.
Undo the 5 fastening screws at the mixing chamber/heat ex-
changer.
Remove bracket.
Pull out the burner together with mixing chamber, fan and flue
silencer to the front (fig. 20).
Clean burner bar with soft brush.
The gas burner has to be disassembled before cleaning the heating
surfaces.
Fig. 19: Dismantle gas burner (PARAMOUNT two 30/40)
Remove gas connection pipe
Remove fastening screws
Remove flue silencer
Remove injector