Technical data

Servicing
64 POTTERTON COMMERCIAL
120-393 632.4 04.08 Fh
Dismantling of the gas burner (PARAMOUNT two 60 D)
Disconnect the connecting lines to the fan.
Disconnect ionisation line.
Disconnect ignition cable.
Disconnect fastening screws of the bracket on the housing lid.
Disconnect the screw connections of the gas connection pipe at
the mixing chamber and the gas valve.
Remove the gas connection pipe and the gas injector.
Disconnect the gas connection pipe at the gas valve and remove
gas valve.
Undo the 5 fastening screws at the mixing chamber/heat ex-
changer.
Remove bracket.
Pull out the burner together with mixing chamber, fan and ea-
haust gas muffler to the front (see figure 19)siehe Abb. 20
Clean burner pipe with soft brush.
Use new seals when installing.
Fig. 20: Dismantle of the gas burner (PARAMOUNT two 60 D)
Pull out burner with mixing
chamber and flue silencer.
Remove bracket.
Remove gas valve.
Remove gas injec-
tor.
Remove gas con-
nection pipe.
Disconnect gas