Owner`s manual

156
tag or "X" for no change. The module will then return to
the main configuration menu (see Section 16.1).
16.10 V50/V73/V74/V75/V76/V86/V87
CONNECT PORT ID ECHO
The V50/V73/V74/V75/V76/V86/V87 has the Connect
Port ID Echo feature. This feature can be enabled or
disabled (default). Connect Port ID Echo is enabled or
disabled by accessing configuration mode and typing "9"
from the main configuration menu. The peripheral
module will respond with:
Connect Port ID Echo is................Disabled
Change it? (Y/N) :
Type 'Y" to change the current setting or N: to exit back
to the main configuration menu.
If Connect Port ID Echo is enabled, the programmed Port
ID will be sent to the host computer whenever a Serial
port is selected. See Section 15.1.4 for more
information on the Port ID.
Note: Connect Port ID Echo is not functional if the
peripheral module is operating in command mode.
16.11 PORT EIA DRIVER PORT ID DRIVER
This item applies to the V86 isolated EIA-484/422
module only. The Port EIA Driver feature is used to
select between EIA-485 and EIA-422 serial interface.
This configuration change is required in addition to
changing the jumper settings on the V86 board to 485
(for EIA-485) or 422 (for EIA-422). The default serial
interface for the V86 is EIA-485.