Overview of Primary Product

Features
Cleaner Operation - The valve operation cuts oil ow almost
instantly when power is cut to the solenoid coil, eliminating coasting
stops that can cause soot formation on shut-down. The Beckett
GeniSys controls or Beckett’s PD timer work well with the CleanCut
pump to bring the burner up to full speed before light-off. See
illustration below.
More Reliable - There are fewer moving parts compared to
conventional pumps and fewer troublesome oil ttings to cause
problems. In addition, all of the moving parts in the CleanCut pumps
have been in use for years in both the US and in Europe.
Higher Capacity - The unique design of the Cleancut pumps deliver
up to 4 gallons per hour at 100 psi. (Note that applications above 3
gph will require an additional valve to meet UL requirements.)
Reduced Load on Motor - Reduces load on the motor during start-up.
Description
The Beckett CleanCut family of pumps has been developed to combine
the benets of a solenoid valve and the superior lift capabilities of
traditional American pumps. We have added an additional supplier
to this product offering, while keeping the eld proven features and
performance benets that have become the standard of the industry.
The Beckett p/n PF20422 is a two-stage pump for use where lift
requirements exceed 12’. The PF20422 is a direct replacement for
Suntec B2VA-8216 when solenoid cutoff is desired. Note: A GeniSys
control with pre-purge or a Beckett PD Timer will be needed for proper
burner operation. See reverse for instructions.
CLEANCUT
®
OIL PUMP
PRODUCT SHEET
Pump Model Numbers
Beckett Part No. Manufacturer Part No. Description
PF20322 A2EA-6527
Single-Stage
4 GPH 120VAC
PF20323 071N1121
Single-Stage
4 GPH 120VAC
PF20422 B2EA-6550
Two-Stage
4 GPH 120VAC
120VAC pumps listed. For pumps with other voltage options listed above,
please call Beckett or visit www.beckettcorp.com for more information.
PD Timer
No control change necessary! If the burner does
not have a control the supports valve-on-delay
(pre purge), Beckett’s PD Timer can be used to
add this function without changing the control.
Specifications
Nozzle Pressure
Range
100-200 PSI
Factory Set
Pressure
100 PSI
Capacity 4 GPH @ 100-150 PSI (#1 & #2 Fuel Oil)
3 GPH @ 100-200 PSI (#2 Fuel Oil)
Operating Fluids #1 & #2 Fuel Oils Meeting ASTM D396 with Biodiesel
blends up to 5% (B5) Viscosity 1.2 – 16 cSt
Inlet/Return
Pressures
10 PSI*
Suction Height One Pipe Supply: 6’ Max.
Two Pipe Supply: 12’ Max. (PF10322 / PF10323)
Two Pipe Supply: 17’ Max. (Two-Stage PF10422)
Rated Speed 3450 RPM Nominal
Ambient temp. 32°F Min. / 140°F Max.
Electrical
Ratings
120 VAC (102V Min. - 132V Max.) 9W Max.
220 / 240 VAC (187V Min. – 264V Max.) 9W Max.
12VDC (10.2V Min. – 16V Max.) 9W Max.
Certification UL, CUL
*System inlet / return pressures must conform to NFPA 31 (3 PSI) as well as
any additional Federal, State, or Local codes.
CleanCut PF20322 CleanCut PF20323 CleanCut XL PF20422