Over-temp 2 Wait while the tester cools down.
Fault Voltage 4
Check the installation, in particular, the voltage
between N and PE.
Excessive Probe
Resistance
6
Put the stakes deeper into the soil. Tamp down the soil
directly around the stakes. Pour water around the stakes
but not at the earth ground under test.

To select a power-on option, press and the function key simultaneously and then release
the
button. Power-on options are retained when the tester is turned OFF. See Table
below.
UK - Mode Selected Automatic Lead
Swapping Mode Selected
Figure 7. Lead Swapping Modes
 
Line and Neutral Swap mode. Two modes of operation are available. You
can configure the tester to operate in L-n mode or L-n n-L mode, see Figure
7.
•InL-nmode,theLandNphaseconductorsmustNEVERbereversed.This
is a requirement in some regions including the UK. The
icon appears
on the display indicating that the system L and N conductors are swapped
and testing is inhibited. Investigate and rectify the cause of this system
fault before proceeding. L-n mode also changes the RCD x1/2 trip time
duration to 2 seconds as required in the UK.
•InL-nn-Lmode,theunitallowstheLandNphaseconductorstobe
swapped and testing will continue.
Note: In locations where polarized plugs and outlets are used, a swapped
lead icon (
) may indicate that the outlet was wired incorrectly. Correct
this problem before proceeding with any testing.
Fault voltage limit. Toggles the fault voltage between 25 V and 50 V. The
default is 50 V.
View the tester serial number. Primary display shows the initial four digits
and the secondary display shows the next four digits.
Continuity beeper toggle. Toggles the continuity beeper on and off. The
default is on.