User Manual

15
WWarning
 

 
 
 

Note: If the L and N terminals are reversed, the tester will auto-swap them internally and
continue testing. If the tester is configured for UK operation, testing will halt and you will
need to determine why the L and N are swapped.
This condition is indicated by symbol (
).
Type A and type B RCDs do not have the 1000 mA option available.

1. Turn the rotary switch to the
position.
2. Press F1 to select the RCD current rating (10, 30, 100, 300, 500, or 1000 mA).
3. Press F2 to select a test current multiplier (x ½, x 1, x 5, or Auto). Normally you will use x
1 for this test.
4. Press F3 to select the RCD test-current waveform:
– AC current to test type AC (standard AC RCD) and type A (pulse-DC sensitive RCD)
– Half-wave current to test type A (pulse-DC sensitive RCD)
– Delayed response to test S-type AC (time delayed AC RCD)
– Delayed response to S-type A (time delayed pulse-DC sensitive RCD)
– Smooth-DC current to test type B RCD
– Delayed response to S-type B (time delayed smooth-DC current RCD)
5. Press F4 to select the test current phase, 0° or 180°. RCDs should be tested with both
phase settings, as their response time can vary significantly depending on the phase
Note: For RCD type B (
) or S-type B ( ), you must test with both phase
settings, all three test leads are required.
6. Press and release
. Wait for the test to complete.
•Theprimary(upper)displayshowsthetriptime.
•Thesecondary(lower)displayshowsthefaultvoltagerelatedtotheratedresidual
current.