User Manual

28

 
AC
(sinusoidal)
The waveform is a sinewave starting at zero crossing, polarity
determined by phase selection (0 ° phase starts with low to
high zero crossing, 180 ° phase starts with high to low zero
crossing). The magnitude of the test current is I
P
n x Multiplier
for all tests.
A
(half wave)
The waveform is a half wave rectified sinewave starting at
zero, polarity determined by phase selection (0 ° phase starts
with low to high zero crossing, 180 ° phase starts with high
to low zero crossing). The magnitude of the test current is
2.0 x I
P
n (rms) x Multiplier for all tests for I
P
n = 0.01A. The
magnitude of the test current is 1.4 x I
P
n (rms) x Multiplier for
all tests for all other I
P
n ratings.
B (DC) This is a smooth DC current according to EN61557-6 Annex A



  
[1]

[1]

[1]

[2]
X ½, 1
X 5
Ramp
Auto
Note:
Mains voltage 100 V – 265 V ac, 50/60 Hz
[1] Type B RCDs require mains voltage range of 195 V – 265 V.
[2] Type AC RCDs only.





 
X ½ G 310 ms 2000 ms ± (2% Reading + 2ms)
X ½ S 510 ms 2000 ms ± (2% Reading + 2ms)
X 1 G 310 ms 310 ms ± (2% Reading + 2ms)
X 1 S 510 ms 510 ms ± (2% Reading + 2ms)
X 5 G 50 ms 50 ms ± (2% Reading + 2ms)
X 5 S 160 ms 160 ms ± (2% Reading + 2ms)
Note:
*G – General, no delay
*S – Time delay