User Manual
29
I
PN
AC G, A, B X 1 Less than 300 ms
AC G-S, A-S, B-S X 1 Between 130 ms and 500 ms
AC G, A, B X 5 Less than 40 ms
AC G-S, A-S, B-S X 5 Between 50 ms and 150 ms
I
PN
30 % to 110 % of
RCD rated current
[1]
10 % of I
PN
[2]
300 ms/step 500 ms/step ±5 %
Notes
[1] 30 % to 150 % for Type A I
PN
>10 mA
30 % to 210 % for Type A I
PN
= 10 mA
20 % to 210 % for Type B
Specified trip current ranges (EN 61008-1):
50 % to 100 % for Type AC
35 % to 140 % for Type A (>10 mA)
35 % to 200 % for Type A (≤10 mA)
50 % to 200 % for Type B
[2] 5% for Type B
Telaris ProInstall-200 only. This product is intended to be used to measure installations in
process plants, industrial installations, and residential applications.
Range
200 Ω 0.1 Ω ±(3 % + 5 digits)
2000 Ω 1 Ω ±(5 % + 10 digits)
Range: R
+ R
[1]
2200 Ω 3.5 mA
16000 Ω 500 μA
52000 Ω 150 μA
Note
[1] Without external voltages
128 Hz 25 V
Inhibits test if terminal voltage >10 V ac is detected prior
to start of test.