Install Instructions

10
Tech.Doc - 03/21 - Subject to change. © Belimo Aircontrols (USA), Inc.
ECON-ZIP-COM
ZIP Economizer™ Communication Module
Technical Data
Power supply
AC 24 V ± 20%, 50/60 Hz, class 2 power source
Power consumption rating*
2.5 VA (ECON-ZIP-COM), 6.5 VA
(ECON-ZIP-BASE + ECON-ZIP-COM)
(ECON-ZIP-BASE + ECON-ZIP-COM)
Connectors
1/4" male spade connectors
Environmental
RoHS, conformally coated
Communication interface
RS485 interface, optical isolation max. 1k VDC
(for max.1 min), Pin 4: RS485 Com Gnd, Pin 7:
RS485 Com A, Pin 8: RS485 Com B
Supported remote alarm
normal current: 0.5A, inrush current: 1A
Humidity
5...95% RH non-condensing
Housing
NEMA 1
Housing material
UL94-5VA
Ambient temperature range
-40...+158°F [-40...+70°C]
Storage temperature range
-40...+176°F [-40...+80°C]
Agency listing
cULus acc. to UL873, CAN/CSA C22.2, No.
24-93
*The power consumption is for the control only and does not include connected loads such as actuator,
compressors, fans, and sensors. For transformer sizing, the power consumption of these attached
components must be included.
Wiring Diagram
Dimensions (Inches [mm]) I/O Specifications
Type
Name
Description
Electrical Specifi cation
I/O
Comm
Communication
Interface
RS485 Interface
Optical Isolation max. 1k VDC
(for max. 1min)
Terminal Assignments:
(+) Data B
(-) Data A
GND Ground
Relay
ALM
Diagnostic Alarm
Relay contact 24 V
Normal current: 0.5A
Inrush current: 1A
Product Features
The ZIP Economizer™ Communication Module provides alarm output
with BACnet MST/TP capabilities such as data trending, building
automation integration, and OEM communication integration.
Operation
The ZIP Economizer™ Communication Module has full functionality
when connected to the ECON-ZIP-Base. With its unique keyed slot, it
makes installation a breeze.
AC 24 V Alarm
Light / Pilot Relay