Install Instructions

11
Tech.Doc - 03/21 - Subject to change. © Belimo Aircontrols (USA), Inc.
Installation
Dimensions in Inches [mm]
Avoid mounting in areas where acid fumes or other deteriorating
vapors can attack the metal parts, or in areas where escaping gas or
other explosive vapors are present.
Mount the sensor in a position that will allow for proper clearance
for installation, servicing, wiring, and removal.
Using the dimensions as a reference, mount the 10K Sensor on the
outside of the dampers to measure outside temperature, or inside
the return air duct to measure the return temperature. If mounted
outside, the sensor must be placed within hood behind the outdoor
air fi lter. It needs to be protected from direct exposure to water
(snow/rain) and direct exposure to sunlight (UV radiation).
Secure the sensor with #8 self-tapping screws (included in kit) using
a size 16 or 18 drill.
Wiring Diagram
ZIP Economizer Terminal inputs
SAT (+/-)
SAT (+/-)
OAT (+/-)
OAT (+/-)
RAT (+/-)
RAT (+/-)
ECON-ZIP-10K
ECON-ZIP-10K
ZIP Economizer™ Temperature Sensor
Technical Data
Temperature output signal
NTC 10k Ohm, Type II
Connectors
1/4" female spade insulated connectors,
3 ft. cable
Accuracy
± 0.36°F [± 0.2°C]
Stability drift
less than 0.036°F/yr [0.02°C/yr]
Material
etched Teflon, plenum-rated & FEP jacketed
cable; galvanized t-bracket
Ambient temperature range
-67°F...+176°F [-55...+80°C]