ZIP Economizer
Menu Structure Tables - Settings
Menu Item Parameter Default Range Notes
Zip Code
1
US
00000
5 Digit Num
Setting of either US or Canada code required for Economizer Operation.
Setting the ZIP code automatically confi gures the economizer high limit change
over temperature to comply with local energy code. If the user desires a different
high limit value, this can be modifi ed in the “settings” menu under “high limit
modifi cation”.
Canada
000000
6 Digit Alpha/Num
Setting of either US or Canada code required for Economizer Operation.
Setting the ZIP code automatically confi gures the economizer high limit change
over temperature to comply with local energy code. If the user desires a different
high limit value, this can be modifi ed in the “settings” menu under “high limit
modifi cation”.
Energy
Module I/O
Config
4
ALM
2 Speed Fan Op
ALM
Alarm
2 Speed Fan Op
This is where the Energy Module's output is configured to either Alarm or Indoor
Fan. The default is Alarm, but if desired, can be changed to 2 Speed Fan Op.
Heat Pump
Op
Heat Pump Op
Off
Off
HP (O) = pow = Cool
HP (B) = pow = Heat
HP (W1) = pow = Heat
If the RTU that the economizer is installed in, is a heat pump, then this value shall
be set to one of the following:
(O) = Reversing valve powered for cooling.
(B) = Reversing valve powered for heating.
(W1) = Standard thermostat, reversing valve controlled by internal RTU defrost board.
Devices 1
CC1, CC2, IF, EF
(as connected)
Fan 2 Speed
4
Auto
2
Auto, Available, Not
Available
Allows for 2 speed indoor fan control circuit (IF) to be automatically detected when
wired. If circuit is not automatically detected, the functionality can be manually
enabled by choosing “available.” If there is a desire to disable functionality for
any reason, the operator can choose “not available” and the operation of the
economizer will function as if the device is not installed or confi gured.
Compressor Qty
3
Auto
2
Auto, 1, 2
Allows for up to 2 compressor circuits (CC1, CC2) to be automatically detected
when wired. If circuit is not automatically detected, the functionality can be
manually enabled by setting compressor Qty to 1 or 2.
Exh Fan Install
4
Auto
2
Auto, Installed, Not
Installed
Allows for exhaust fan control circuit (EF) to be automatically detected when
wired. If circuit is not automatically detected, the functionality can be manually
enabled by choosing “available.” If there is a desire to disable functionality for
any reason, the operator can choose “not available” and the operation of the
economizer will function as if the device is not installed or configured.
Humidity
Sensors
OAH (YES/NO)
RAH (YES/NO)
Auto
2
Auto, Installed, Not
Installed
Allows for humidity sensors to be automatically detected when wired. If sensors
are not automatically detected, the functionality can be manually enabled by
choosing "installed".
If there is a desire to disable functionality for any reason, the operator can choose
"not installed" and the operation of the economizer will function as if the device is
not installed or configured.
Devices 2
OAH, RAH,
(as connected)
OAH
5
Auto
2
Auto, Installed, Not
Installed
Allows for the Outside Air Humidity Sensor to be automatically detected when
wired for enthalpy change over strategy. If the sensor is not automatically
detected, the humidity sensor can be manually enabled by choosing “installed.” If
there is a desire to disable functionality for any reason, the operator can choose
“not installed”, and the operation of the economizer will function as if the device is
not installed or configured.
RAH
5
Auto
2
Auto, Installed, Not
Installed
Allows for the Return Air Humidity Sensor to be automatically detected when wired
for differential enthalpy change over strategy. If the sensor is not automatically
detected, the humidity sensor can be manually enabled by choosing “installed.” If
there is a desire to disable functionality for any reason, the operator can choose
“not installed,” and the operation of the economizer will function as if the device is
not installed or configured.