Install Instructions

32
Tech.Doc - 03/21 - Subject to change. © Belimo Aircontrols (USA), Inc.
Menu Item Parameter Range
1
Notes
Economizer
Operation by
(displays high
limit change over
strategy based on
detected connected
sensors)
Fixed dry bulb
Displayed when only OAT sensor connected (ECON-ZIP-10K).
Fixed enthalpy + Fixed dry
bulb
Displayed when an OAT and OAH sensor connected (ECON-ZIP-TH).
Diff enthalpy + Fixed dry
bulb
Displayed when an OAT and OAH sensor used but either value is not present.
Differential dry bulb
Displayed when an OAT and RAT sensor are connected (two ECON-ZIP-10K).
OAE>RAE
OA>RA enthalpy differential
Displayed when an OAT and OAH sensor connected and a RAT and RAH sensor connected (two ECON-ZIP-TH
sensors).
Econ High Limit
xx Temp (°F - °C)
xx Enthalpy (Btu/lb - kJ/kg)
This is the economizer to mechanical cooling change over high limit set by ZIP Code / Postal Code and
connected sensor choice.
US/Canada Zip Code/Postal Code Displays the ZIP Code / Postal Code entered in Settings.
Run Time Comp 1 Hours
Displays the operating time when CC1 is powered to enable compressor 1 to operate (this includes Integrated
Cooling periods). Logged time can be reset through menu for seasonal maintenance, equipment repairs, or for
other individual needs.
Run Time Comp 2
5
Hours
Displays the operating time when CC2 is powered to enable compressor 2 to operate (when 2 stages are
available). Logged time can be reset through menu for seasonal maintenance, equipment repairs, or for other
individual needs.
Run Time Econ Hours
Displays the operating time when in Free Cooling. (Does not include Integrated Cooling periods). Logged time
can be reset through menu for seasonal maintenance, equipment repairs, or for other individual needs.
Run Time Mech Hours
Displays the totaled time when CC1 and CC2 have been powered. Logged time can be reset through menu for
seasonal maintenance, equipment repairs, or for other individual needs.
Run Time DCV Hours
Displays the time when energy is saved by resetting the damper position within range from Vent Min Pos (ECOM)
DCV Min Pos (DCVM). (Note: in DCV Heating and mechanical cooling is possible). Logged time can be reset
through menu for seasonal maintenance, equipment repairs, or for other individual needs.
Run Time Integra Hours
Displays the operating time when in Free Cooling with Damper at 100% and CC1 is powered to enable
compressor 1 to operate. Logged time can be reset through menu for seasonal maintenance, equipment repairs,
or for other individual needs.
Run Time Vent Hours
Displays the operating time when in Occupied state and Ventilation mode is active (G is On). Logged time can be
reset through menu for seasonal maintenance, equipment repairs, or for other individual needs.
Run Time Heating Hours
Displays the operating time when in Heating (W1 is On). Logged time can be reset through menu for seasonal
maintenance, equipment repairs, or for other individual needs.
Run Time Unoccup Hours
Displays the operating time when in Unoccupied state (G is Off). Logged time can be reset through menu for
seasonal maintenance, equipment repairs, or for other individual needs.
Run Time FP Hours
Displays the Operating time when in Freeze Protection. Logged time can be reset through menu for seasonal
maintenance, equipment repairs, or for other individual needs.
Firmware xx.x.xxxx Displays software revision version.
1. When an alarm is present the value may not be displayed
2. Only visible when Humidity Sensor is present
3. Only visible when Return Air Temperature Sensor is present
4. Only visible when Energy Module is connected and the accessory component is powered, wired, terminated to the Energy Module, and has been setup in Settings menu
5. Only visible when 2 compressors are detected or enabled
6. Requires that the Energy Module is connected, 2 speed fan is installed, and the accessory Component or Device is powered, wired, terminated to the Energy Module, and has been setup in
Settings menu
ZIP Economizer
Menu Structure Tables