Install Instructions

47
Tech.Doc - 03/21 - Subject to change. © Belimo Aircontrols (USA), Inc.
ZIP Economizer
BACnet Object Descriptions
Object Name Object
Type /
Instance
Description Values Values
Default /
Unit
COV
Increment
COV
Increment
Default
Access
Device_Name
Device[x]
RelPosDmpFb
AI [1]
Relative Damper Position
Feedback in %
-1110
[%]
1…110
5
R
SAT
AI [2]
Temperature Supply Air
-50160
F]
0.5…160
2
R
OAT
AI [3]
Temperature Outdoor Air
-50160
F]
0.5…160
2
R
OAH
AI [4]
Humidity OutdoorAir in
%RH
6…110
[%]
1…110
2
R
OAE
AI [5]
Enthalpy Outdoor Air
0…50
[Btu/lb]
0.5…50
1
R
RAT
AI [6]
Temperature Return Air
-50160
F]
0.5…160
2
R
RAH
AI [7]
Humidity ReturnAir in
%RH
6…110
[%]
1…11 0
2
R
RAE
AI [8]
Enthalpy Return Air
0…50
[Btu/lb]
0.5…50
1
R
CO2Concentration
AI [9]
CO2 concentration in
ppm
250…2200
[ppm]
5…220 0
50
R
SpDmpPos
AI [10]
Damper position output
in %
0…100
[%]
1…100
2
R
RunTimeCompressor1
AI [11]
Runtime compressor 1 in
h
-
[h]
-
-
R
RunTimeCompressor2
AI [12]
Runtime compressor 2in
h
-
[h]
-
-
R
RunTimeEcon
AI [13]
Runtime free cooling in h
-
[h]
-
-
R
RunTimeMechanical
AI [14]
Runtime mechanical
cooling in h
-
[h]
-
-
R
RunTimeDCV
AI [15]
Runtime Demand Control
Ventilationin h
-
[h]
-
-
R
RunTimeIntegrated
AI [16]
Runtime integrated
cooling in h
-
[h]
-
-
R
RunTimeVentilation
AI [17]
Runtime ventilation in h
-
[h]
-
-
R
RunTimeHeating
AI [18]
Runtime heating in h
-
[h]
-
-
R
RunTimeUnoccupied
AI [19]
Runtime unoccupied in h
-
[h]
-
-
R
RunTimeFreezeProtection
AI [20]
Runtime freeze
protectionin h
-
[h]
-
-
R
DeviceProductionDate
AI [21]
Date of device production
-
-
-
-
R
CO2Network
AO [1]
Networked CO2 value in
ppm
250…2200
8888
[ppm]
5…220 0
50
C
OAHNetwork
AO [2]
Networked Outdoor Air
Humidityin %RH
5…100
8888
[%]
1…100
2
C
OATNetwork
AO [3]
Networked Outdoor Air
Temperature
-50160
8888
F]
0.5…160
2
C
RAHNetwork
AO [4]
Networked Return Air or
space Humidityin %RH
5…100
8888
[%]
1…100
2
C
RATNetwork
AO [5]
Networked Return Air or
space Temperature
-50160
8888
F]
0.5…160
2
C
RemoteDmpOverridePos
AO [6]
DMP override Pos in
% (Enabling this disables:
FC,VENT,DCV,Purge)
0…100
8888
[%]
1…100
2
C
Access: R = Read, W = Write, C = Commendable with priority array