Install Instructions

50
Tech.Doc - 03/21 - Subject to change. © Belimo Aircontrols (USA), Inc.
ZIP Economizer
BACnet Object Descriptions
w
ww.belim o.c om
T
5-PICS Belimo ZIP Economizer en v1.0 01.2019 Subject to changes
OccupancyCommand MO [1] Occupancy (Fan) command 1: Enabled
2: Disabled
3: Relinquished
3 C
PurgeCommand MO [2] Request Purge mode when
PurgeOpe rationEn is enabled
1: Enabled
2: Disabled
3: Relinquished
3 C
W1Command MO [3] Heating command 1: Enabled
2: Disabled
3: Relinquished
3 C
Y1Command MO [4] Stage 1 cooling command 1: Enabled
2: Disabled
3: Relinquished
3 C
Y2Command MO [5] Stage 2 cooling command 1: Enabled
2: Disabled
3: Relinquished
3 C
Object Name Object
Type /
Instance
Description
Values
Default
Access