ZIP Economizer
BACnet Object Descriptions
51
Tech.Doc - 01/20 - Subject to change. © Belimo Aircontrols (USA), Inc
.
Z
IP Economizer
BACnet Ob
j
ect Description
s
ID Name Description
1
Virgin
2
Auto
3
Manual
4
Factory Test
5
Acceptance Tests
6
Free Cooling
7
Integrated Cooling
8
Mechanical Cooling
9
DCV
10
Ventilation
11
Heating
12
Unoccupied
13
Purge
14
Freeze Protection
15
Brownout
16
PCB Test
17
Recovery
18
Damper Scaling
ID BACnet Name Description
1 OAT_OR OAT sensor out of range
2 OAT_ND OAT sensor not detected
3 OAH_O R OAH sensor out of range and single enthalpy error active
4 OAH_ND OAH sensor not detected and single enthalpy error active
5 OAHDT OAH sensor out of range and dual enthalpy error active
6 OAH OAH sensor not detected and dual enthalpy error active
7 RAT_OR1 RAT sensor out of range and RAT temperature error active
8 RAT_ND1 RAT sensor not detected and RAT temperature error active
9 RAT_OR2 RAT sensor out of range and RAT enthalpy error active
10 RAT_ND2 RAT sensor not detected and RAT enthalpy error active
11 RAH_OR RAH sensor out of range
12 RAH_ND RAH sensor not detected
13 RHnoOAH RAH sensor detected but no OAH sensor detected
14 RHnoRAT RAH sensor detected but no RAT sensor detected
15 SAT_ OR SAT sensor out of range
16 SAT_ND SAT sensor not detected
17 Y2noY1 Y1 inactive but Y2 active
18 SAT_Er1 Compressor 1 error active (no adequate SAT drop during compressor operation)
19 SAT_Er2 Compressor 2 error active (no adequate SAT drop during compressor operation)
20 Dmp_Pos Actuator/Damper feedback missing
21 SAT_Er3 Actuator/Damper SAT error (DmpPos = 100%, OAT = SAT)
22 Dmp_S tk Actuator/Damper stall (Feedback does not change)
23 EM_ND Energy module state changes during operation
24 EF_ND Exhaust fan not detected (Exhaust fan setting = installed)
25 CC1_ND Compressor 1 not detected (Compressor quantity setting >= 1)
26 CC2_ND Compressor 2 not detected (Compressor quantity setting = 2)
27 IF_ND Indoor fan part load not detected (Indoor fan setting = installed)
28 CO2_ND CO2 sensor not detected
29 CO2_O R CO2 sensor out of range
30 W1and Y1 Y1/Y2/W1 error, heating and cooling request simultaneous
31 No_Alm No alarm