User manual

22
WARNING:
DO NOT output 10 A or more with only one pair of
(+) and (-) terminals. Both (+) and (-) terminals
must all be connected for applications requiring
more than 10 A output. Each terminal can only
accept a maximum of 10 A. Exceeding this may
damage the power supply.
Table 2- Wire Gauge Rating
AWG
10
12
14
16
18
20
22
24
26
28
Imax(A)
40
25
20
13
10
7
5
3.5
2.5
1.7
mΩ/meter
3.3
5.2
8.3
13.2
21
33.5
52.8
84.3
133.9
212.9
Rear Panel Output
+S
+
+
-
-
-
S
DUT
+ -
+S + - -S
Remove shorting bars
Front Panel Output
For 10 A or higher current output