Installation guide

BlackDiamond 20808 Switch Hardware Installation Guide
25
3 BlackDiamond 20808 Power Supplies
This chapter includes the following sections:
Overview of the BlackDiamond 20808 Power Supplies on page 25
AC Power Supply on page 25
DC Power Supply on page 27
NOTE
For central DC power connections, the 1900 W DC PSU is intended to be installed only in restricted access
locations (for example, a dedicated equipment room, equipment closet, or central office) in accordance with Articles
110-16, 110-17, and 110-18 of the National Electric Code, ANSI/NFPA-70. All wiring methods involving the DC
input cable assembly must be performed according to the relevant articles of the National Electrical Code.
WARNING!
Field operators must not attempt to open the PSU enclosure for any reason; the PSU does not contain user-
serviceable parts. In the event of failure, return the defective PSU to Extreme Networks for repair or replacement.
Overview of the BlackDiamond 20808 Power Supplies
The BlackDiamond 20808 switch can be powered by either AC or DC power supplies (PSUs). Power
supplies in the BlackDiamond 20808 switch are fully fault tolerant and load-sharing in an N+1
configuration. After the system is properly configured, if one PSU fails, the others provide sufficient
power to operate a fully loaded switch.
AC Power Supply
Figure 7 shows the 2400 W AC power supply unit. This power supply can run from 180 to 264 V AC
and delivers 2400 W of power. The power supply bay in the BlackDiamond 20808 switch can
accommodate up to five 2400 W AC PSUs.