Installation guide

DC Power Supply
BlackDiamond 20808 Switch Hardware Installation Guide
27
Fuse
The Extreme Networks 2400 W AC PSU line and neutral legs are both fused. Power to the switch may
still be live if the neutral fuse is open. This is not a field operator replaceable fuse.
WARNING!
Field operators must not attempt to configure or replace fuses in Extreme Networks 2400 W AC PSUs! In the event
of failure, immediately return the defective Extreme Networks 2400 W AC PSU for a complete replacement.
Power Supply Cords
An AC power cord for use with the 2400 W AC PSU must meet the following requirements:
The power cord must be agency-certified for the country of use and rated for 200-240 V AC.
The power cord must have an IEC 320 C19 connector for connection to the PSU.
The power cord must have an appropriately rated and approved wall plug applicable to the country
of installation.
The power cord must be less than 3 meters (10 feet) long.
The wire size must be a minimum of 14 AWG (2.06 mm
2
) copper-stranded.
DC Power Supply
Figure 8 shows the Extreme Networks 1900 W DC power supply unit. This power supply can run from
40 to 72 V DC and deliver 1900 W of power. The power supply bay in the BlackDiamond 20808 switch
can accommodate up to five 1900 W DC PSUs.
Figure 8: 1900 W DC PSU