Instructions

7620100 / 7621100 / 7622100 / 7623100
980035700 Rev.001
Magnetic Latch (ML) - draws very low current in the ON or OFF states, and draws moderate current for very
short time when changing state
•StartIsolation(SI)—canbeconguredfortemporaryisolationofHouseloadsfromEnginecircuitduring
enginecrankingtoprotectsensitiveelectronics
•EngineIsolation(EI)—canbeconguredforisolationoftwoengineswhilebotharerunningtoprotect
engineelectronicsandmaximizealternatoroutput
Senses charging on two battery banks
•LEDoutputtoremotelyindicatewhenbatteriesarecombinedorisolated
•Tin-platedcopperstudsformaximumconductivityandcorrosionresistance
•Labelrecessesforcircuitidentication
•Silveralloycontactsprovidehighreliabilityforswitchingliveloads
Includes a Remote Control Contura Switch (2146)
IncludesaDeutschDTMconnector(matingpartnotincludedbutrequired)
Specications 12VDC 24VDC
Wire Size and Current Ratings See table below See table below
ML-Coil Function Bi-stable Bi-stable
AmperageOperatingCurrent continuous <13mA@25°Cnominalvoltage <13mA@25°Cnominalvoltage
changingstage(20ms) <7A@25°Cnominalvoltage <4A@25°Cnominalvoltage
OperatingVoltage(contacts) 9-16VDC 18-32VDC
ControlVoltage 9-16VDC 18-32VDC
RelayContactPosition:
-Combine(30sec.) 13.5V 27.0V
-Combine(90sec.) 13.0V 26.0V
-OpenLow(10sec.) 12.35V 24.7V
-OpenLow(30sec.) 12.75V 25.5V
-OpenHigh 16.2V 32.4V
LiveCurrentSwitching 300A@12VDC-10,000Cycles 150A@24VDC-10,000Cycles
Terminal Stud Size 3/8"-16 3/8"-16
MaximumTerminalStudTorque 140in-lb(15.8N•m) 140in-lb(15.8N•m)
Ring Terminal Size 3/8" (M10) 3/8" (M10)
TerminalRingDiameterClearance 1.18" (30 mm) 1.18" (30 mm)
ControlCircuitCurrentDraw <40mA <40mA
RemoteControlConturaSwitch
Action SPDT,ON-OFF-ON
Seals Internal&ExternalGasketPanelSeal
MountingHole 0.83x 1.45 (21.08 mm x 36.83 mm)
LEDRating 100,000hourshalf-life
HarnessConnector DeutschDTMSeriesDTM06-6S
MatingPartRequirements seeLADDIndustriesatwww.laddinc.com
RequiredReceptacleShell DTM-04-6P
*
Wedgelock WM-6P
Terminal Pins 1060-20-0122
Sealing Plugs 0413-204-2005
HandCrimpTooling DTT-20-0
RegulatoryMeets ISO 8846 and SAE J1171 external ignition protection requirements, CE marked, Rated IP66
* Special modifications are available depending on customer requirements. No polarization on standard product.
† Quantity depends on optional wire connections. The total number of pins and sealing plugs is 6.
‡ Required for hand assembly of wires and terminal pins.
MarineElectricalProd
ucts
PN Termination
Manual
Control
Control
Circuit
7620100 DeutschConnector No 12VDC
7621100 DeutschConnector No 24VDC
PN Termination
Manual
Control
Control
Circuit
7622100 DeutschConnector Yes 12VDC
7623100 DeutschConnector Yes 24VDC
ML– ACR
Automatic Charging Relays

Guarantee
BlueSeaSystemsstandsbehinditsproductsforaslongasyouownthem.
Find detailed information at www.bluesea.com/about. For customer service, call 800.222.7617.
OverviewofApplication
The ML-Series ACR automatically combines batteries during charging, and isolates batteries when there is no
charging sensed on either battery bank.
ML-Series ACR Function 12 Volt DC Operation 24 Volt DC Operation
Automatically combines battery
banks when sensed voltage
levels are:
Above 13.5V for 30 sec.
Above 13.0V for 90 sec.
Above 27.0V for 30 sec.
Above 26.0V for 90 sec.
Automatically isolates battery
banks when sensed voltage
levels are:
Below 9.6V (undervoltage lockout)
Below 12.35V for 10 sec.
Below 12.75V for 30 sec.
Above 16.2V (overvoltage lockout)
Below 19.2V (undervoltage lockout)
Below 24.7V for 10 sec.
Below 25.5V for 30 sec.
Above 32.4V (overvoltage lockout)
StartIsolationorEngineIsolation.Theisolationinputsenableoneoftwofunctionsdependingon
howtheinputsarecongured.
NOTE: The ML-Series ACR can be congured for Start Isolation or Engine Isolation, but not both.
StartIsolation-Temporaryisolation(35 minutes) of house loads from the engine circuit during engine
crankingtoprotectsensitiveelectronics.CongureStartIsolationwhenthereareheavycrankingloads
causingsagsandspikesthatmightdamageelectronicsintheHousecircuit.Seepage3.
EngineIsolation-Isolatetwoengineswhilebotharerunningtoprotectengineelectronics,andto
maximizealternatoroutput.CongureEngineIsolationwhentheenginemanufacturerrequiresit,and
whenthereareseparatebatteriesforeachengine.Seepage3.
UndervoltageorOvervoltageLockout.
• Undervoltagelockoutpreventsbatteriesfrombeingcombinedwheneitherbatteryisbelow9.6V@12VDC
operationor19.2V@24VDCoperation.
• Overvoltagelockoutpreventsbatteriesfrombeingcombinedwheneitherbatteryisabove16.2V@12VDC
operationor32.4V@24VDCoperation.
ControlSwitchRemoteOperation. OptionalConturaControlSwitch—sustained(SPDT)ON-OFF-ON.
TheControlSwitchshouldbemountedinaconvenientlocationnearhelmcontrolstoallowforquickaccess.
NOTE: Alternatively use a momentary (SPDT) (ON)-OFF-(ON) or momentary push button switch to provide cross connect and/or battery isolation.
To cross connect
(combine) battery banks
Switchto“ON”combinesbatterybankstoprovidemorebatterypowerinhard
starting situations.
To isolate battery banks
Switch to “OFF”- when the battery banks are isolated using the Control
Switch, the battery banks remain isolated, and for at least 30 seconds after
thecontrolswitchisreturnedtothe“AUTO”position.
ControlSwitchRemoteIndicationorML-ACRStatus
NOTE: The remote switch has two LEDs (top and bottom). These LEDs operate simultaneously-either they are both ON or both OFF.
page1of4
LEDINDICATION ACRSTATEORCONDITION
RemoteSwitchSetto“AUTO”ornoRemoteSwitchInstalled
LEDsOFF Batteries are isolated
LEDsON Batteries are combined
LEDsslowsteadyblink,ON-OFF StartorEngineIsolationiscausingbatteriestobeisolated
LEDsquicksteadyblink,ON-OFF
Undervoltage lockout--either battery is below 9.6V@12V DC
operation or 19.2V@24V DC operation.
Overvoltage lockout--either battery is above 16.2V@12V DC
operation or 32.4V@24V DC operation.
RemoteSwitchSettoOVERRIDE“ON”or“OFF”—Automaticoperationissuspendedfor10minutes
afterremoteswitchisreturnedto“AUTO”
LEDsdoubleblink,
Blink-Blink-Pause,Repeat
Manual override--check ACR for switch states OR
ACR mechanical failure
WireSizeandCurrentRatings
Wire Size
Cranking
30 sec.
Intermittent
5 min.
Continuous
(UL 1107)
2/0AWG(70mm²) 1,000A 400A 225A
4/0AWG(120mm²) 1,100A 400A 300A
2×4/0AWG(2x120mm²) 1,450A 700A 500A