Specifications

22
Gas Conversion and Specifications
Gas Regulator
- NAT Gas / LPG / Butane Only.
NOTE: The regulator supplied is convertible
between Natural Gas and LP Gas, but
it’s outlet pressure is fixed ex-factory
and is NOT to be adjusted.
1. Ensure that the gas supply is turned 'Off' at
the mains.
2. Unscrew the hexagonal cap (23mm A/F)
from the regulator.
3. Un-clip the plastic pin from the cap, reverse
the pin and re-fit it back to the cap the
correct way for the gas type to be used.
(Either ‘LP’ or ‘NAT’ should be visible
on the flank of the pin once re-fitted to
the cap).
4. Screw the cap back into the regulator hand
tight only.
- Town Gas Only.
1. Unscrew and remove the slotted cap from
the regulator.
2. Turn on the gas supply and the appliance.
3. Adjust the pressure adjusting nut to achieve
the correct burner operating pressure.
NOTE: The operating pressure to be measured
at the manifold test point and with all
burners operating at the 'High Flame'
setting.
4. Turn off the mains gas supply and bleed the
gas out of the appliance gas lines.
5. Turn on the gas supply and the appliance.
6. Verify the operating pressure remains
correct (Re-adjust the regulator if required).
7. Screw the cap nut back onto the regulator.
NOTE, Pin rotated
for Natural Gas
NOTE, Pin rotated
for LPG
Pressure Adjusting
Screw
Cap Nut
Fig 16
Fig 17