DS9400 Series Release Notes for Firmware V2.
DS9400 Series | Release Notes for Firmware V2.07 | Trademarks Upgrade Information Trademarks If this firmware is installed in a control panel that has been running version 1.x software, it is necessary to erase the old programming in the control panel and reselect the control panel type when the control panel is first powered up. Be careful to select “1-DS9400”- an incorrect selection cannot be undone.
DS9400 Series | Release Notes for Firmware V2.07 | 5.0 . • • Wheelock Sync Protocol. This feature no longer requires the Detection Systems D411/D412 in order to produce Temporal Code 3. Auto Silence Operation. The auto-silence operation is now correctly processed on a system configured to use the autosilence feature that powers up with a trouble condition. • Reorganized Phone Programming Menu.
DS9400 Series | Release Notes for Firmware V2.07 | 7.0 • DS9431 Accidental Removal (DS9400M only): On control panels running firmware version 2.02 or earlier, if the wires on the keypad option bus are momentarily shorted for less than a second, the DS9431 Multiplex Expansion Module may stop working. If this occurs, the display will show “MUX NOT DETECTED” and the Trouble buzzer will sound. If the */Clear key is pressed, the DS9431 will be uninstalled. Firmware version 2.03 corrects this problem.
DS9400 Series | Release Notes for Firmware V2.07 | 7.0 . • • Manual Battery/NAC Test during AC Fail: Manually initiating a battery test (Test Menu, Option 4) when AC has failed will now correctly display the current battery voltage. However, if a user at the control panel requests a manual battery test within five seconds after AC power fails, the system may shut down until AC power returns.
DS9400 Series | Release Notes for Firmware V2.07 | 8.0 8.0 New Features since Firmware Version 1.X • Supports the DS9431 Multiplex Expansion Module to add addressable points (247 additional points, including input modules and I/O modules) • User codes expanded to 100 with DS9431 installed • History log expanded to 499 events with DS9431 installed • Supports remote programming 9.0 Known Issues with Firmware Version 2.
DS9400 Series | Release Notes for Firmware V2.07 | 9.0 Known Issues with Firmware Version 2.07 . • 5. 6. Temporarily swap lines 1 and 2 on the control panel and see if the problem indication moves to the control panel’s other phone line channel, in which case the phone line is causing the problem rather than the line monitor. Confirm that the fault message is “phone fault” and not “Comm fault”.
Bosch Security Systems 130 Perinton Parkway Fairport, NY 14450-9199 Customer Service: (800) 289-0096 Technical Support: (888) 886-6189 © 2006 Bosch Security Systems 36925V