Specifications

Page 24 from 63
6720649497 SM HP270-1 2012/09 en
Electric test to the compressor:
The compressor has some electrical connections and a temperature limiter thermostat that ensure its protection.
Using a multimeter, is possible to control its functionality, nevertheless the HMI will detect if compressor is running.
Cables and cover protection have clear identification of the different connections.
R – Main electro valve
S – Auxiliary electro valve
C – Common
Pict.28 – Compressor electrical connections and thermal protection
Checking Continuity and Resistance ()
Between C – R > 0 Mitsubishi = 4.7 / Highly = 5.84
Between C – S > 0 Mitsubishi = 8.2 / Highly = 7.62
Between R – S > 0
Pict.29 – Testing compressor
C
R
S
R