Installation Guide

FPP-RNAC-8A-4C | Operation and Installation Guide | 4.0 DIP Switch and Option Bus Settings
18 Bosch Security Systems, Inc. | 8/09 | F01U025431-02
4.2 Switch S2
Use Switch S2 to set the following (refer to Table 8):
NAC output control
AC failure delay time – 0, 1, 3, and 6 hour delay
Option bus address – Bus Addresses 1 to 14
Table 8: DIP Switch S2 Settings
Position Name
CNTRL
ALL/
CNTRL 2
AC
DELAY 1
AC
DELAY 0
OPTION
ADDRESS 4
OPTION
ADDRESS 3
OPTION
ADDRESS 2
OPTION
ADDRESS 1
Position Number 0 1 2 3 4 5 6
NAC Output Control Options
NAC Input 1 controls
NAC Outputs 1 and 2.
NAC Input 2 controls
NAC Outputs 3 and 4.
OFF
NAC Input 1 controls all
four NAC Outputs
ON
AC Failure Delay Reporting Options
No delay in AC failure reporting; the
unit signals an AC Failure
immediately.
OFF OFF
AC failure reporting delay = 1 hour. OFF ON
AC failure reporting delay = 3 hours ON OFF
AC failure reporting delay = 6 hours ON ON
Option Bus Settings
Disabled OFF OFF OFF OFF
Address 1 OFF OFF OFF ON
Address 2 OFF OFF ON OFF
Address 3 OFF OFF ON ON
Address 4 OFF ON OFF OFF
Address 5 OFF ON OFF ON
Address 6 OFF ON ON OFF
Address 7 OFF ON ON ON
Address 8 ON OFF OFF OFF
Address 9 ON OFF OFF ON
Address 10 ON OFF ON OFF
Address 11 ON OFF ON ON
Address 12 ON ON OFF OFF
Address 13 ON ON OFF ON
Address 14 ON ON ON OFF
Address 15
Reserved