Installation Guide

FPP-RNAC-8A-4C | Operation and Installation Guide | 5.0 FPP-RNAC-8A-4C Local Status Display
22 Bosch Security Systems, Inc. | 8/09 | F01U025431-02
Table 10: Local Status Display LED Functions (continued)
LED Label Color Description
3 SYSTEM Yellow Blink Count Description
TROUBLE (The Trouble Relay activates or changes state.)
(display priority)
1 Any memory fault (RAM, FLASH, watchdog,
unexpected interruptions, stack corruption).
2 Power supply overvoltage.
3 Low battery or missing battery
4 Battery charger circuit trouble.
5 Auxiliary power overcurrent condition – the current is
measured at the Auxiliary Power Port output.
6 System overcurrent – The combined currents
measured at each NAC output together with the
Auxiliary Power Port output.
7 Power supply output voltage is low.
STEADY The SYS TRBL LED and the Trouble Relay are
active when the Flash Programming module is
connected.
4 GROUND
FAULT
Yellow Ground Fault - Indicates that the NAC output wiring is not connected properly to
an external source or ground.
The Trouble Relay is deactivated.
5 TRBL1 Yellow Output 1 has an open or shorted EOL
The Trouble Relay is deactivated.
6 TRBL2 Yellow Output 2 has an open or shorted EOL
The Trouble Relay is deactivated.
7 TRBL3 Yellow Output 3 has an open or shorted EOL
The Trouble Relay is deactivated.
8 TRBL4 Yellow Output 4 has an open or shorted EOL
The Trouble Relay is deactivated.
Figure 13: FPP-RNAC-8A-4C LEDs
INPUT ACTIVE
AC OK
SYSTEM TROUBLE
GROUND FAULT
TROUBLE 4
TROUBLE 3
TROUBLE 2
TROUBLE 1