1.8 Expander Supervision
A watchdog supervises the operation of the
FPP-RNAC-8A-4C processor and attempts to restart
it if it fails. If the processor does not restart, or the
power fails entirely, the installer-supplied EOL device
disconnects from the input to report the trouble
condition. If power is available, the System Trouble
LED lights if the system encounters an error.
1.9 Auxiliary Power Supply
The FPP-RNAC-8A-4C can be wired to supply
unsupervised constant auxiliary power through its
NAC outputs. Refer to Section
3.7.2 Auxiliary Circuits
on page
16 for additional information.
2.0 Installing the FPP-RNAC-8A-4C
The FPP-RNAC-8A-4C board and the enclosure are shipped together. The board, however, needs to be
mounted into the enclosure. Hardware for mounting the board in the enclosure is supplied in the hardware
pack.
Figure 1: FPP-RNAC-8A-4C Remote NAC Power Supply Board
T
R
O
U
B
L
E
T
R
O
U
B
L
E
AC
I
N
P
U
T
1
I
N
P
U
T
2
EOL
REF
O
U
T
P
U
T
4
O
U
T
P
U
T
3
O
U
T
P
U
T
1
O
U
T
P
U
T
2
OPTION BUS
R Y G B
- AUX POWER +- BATTERY +
REPLACE WITH 15A
BLADE TYPE FUSE
BOSCH
4998149856
INPUT ACTIVE
AC OK
SYSTEM TROUBLE
GROUND FAULT
TROUBLE 4
TROUBLE 3
TROUBLE 2
TROUBLE 1
TROUBLE
RESET
FLASH
PROGRAMMING
PORT
GROUND FAULT
OPEN = DISABLE
CLOSE = ENABLE
1
2
3
4
8
9
10
11
12
13
14
5
6
7
15
16
1 AC Input Select Switch 120/240 VAC
2 AC Power Input 120/240 VAC
3 Option bus
4 Ground fault switch
5 Flash programming port
6 TROUBLE RESET button
7 AC trouble relay output
8 Trouble relay output
9 NAC inputs
10 EOL reference resistor (1k to 20k)
11 NAC outputs
12 Auxiliary 24V filtered and regulated output
power
13 Replaceable 15A fuse
14 Battery input
15 Configuration DIP switches
16 Status LEDs