User guide

4. Remove the plate and carefully cut through the overlay with a sharp knife.
5. Feed the pre-wired terminal block and wires through the hole now exposed in the Control Panel. Click the
Programmer in place from the front.
6. Screw the terminal block and Legend Plate to the support bracket the LEN going uppermost.
Wiring Programmer
1. Remove Red Wire (F) from Limit Thermostat Terminal (G) and 3 way Terminal block (H) and discard.
2. Fit Brown Wire (J) spade onto vacated Terminal (G).
3. Secure Red Wire (K) into the vacated hole in 3 way terminal block (H).
4. Fit Blue Wire (L) in alongside the existing Blue Wire (M) in 3 way terminal block (H).
5. Remove Black Wire (N) from terminal block (H) and connect this into the single connector which is wired to
number 9 of terminal block (D).
6. Connect appropriate flag terminals to the programmer as shown in fig 4:12.C.
7. Fit Green/Yellow Earthwire (P) securely to Earth Post.
8. Make all necessary connections to the 12 way block (D) as Wiring Diagram Section.
9. Check all connections refit Control Panel back cover.
10. Restore mains supply to boiler - digital display will show 12:00.