User guide

*Where the terminal is within 1m of any plastic material, such material should be shielded from the effects of
the combustion products of the flues
NOTE:- Whilst the dimensions in BS 5410 are shown in the table, it is stressed that possible variances
in local site conditions may not always be obvious and that if in any doubt the dimensions in brackets
should be observed.
BOULTER BUDERUS would be pleased to advise on any difficult positioning
Fig. 5.4a Balanced Flue Terminal Positions
BOULTER BUDERUS CAMRAY 5
PAGE 25
5:5 TERMINAL GUARDS
When the terminal is positioned where there is the possibility of accidental contact by persons, or of damage
to the terminal, an approved guard is necessary (Boulter Code FL26160).
Generally, exhaust 2 metres above ground level alleviates the necessity for a guard.
A
suitable guard is available from BOULTER BUDERUS as shown below.
5:6 HORIZONTAL FLUE TERMINAL
The Terminal for Horizontal Balanced Flue is secured to the wall by means of four screws. The indexing plate
should have its four edges siliconed to the outside wall to provide a weather seal.
C From any Internal Corner 300
(900)
D Above Ground 300
(600)
E From a surface facing the Terminal 600
(1200)
F From a Terminal facing a Terminal 1200
G Vertically between Two Terminals on the same wall 1500
H Horizontally between Two Terminals on the same wall 750
(1200)
J From any External Corner 300
(600)
K Horizontally from any Opening, Air Brick, Window or Door 600
L Vertical Flue from Wall (Flat or Pitched Roof) 750
Pa
g
e 38 of 67
14/04/2005file://D:\PL47000\PL47000.htm