Troubleshooting guide

10
5. The minimum clearances to combustibles for this water heater are: two (2) inches (5.1 cm) from the sides and
rear, two (2) inches (5.1 cm) from the front of the burner access box, sixteen (16) inches (40.6 cm) from the top
jacket, zero (0) inch (0 cm) from the air intake boot and vent tubes and twelve (12) inches (30.5 cm) in any
direction from the direct vent terminal. A minimum of 30 inches (76.2 cm) front clearance from the burner access
panel is necessary for inspection and servicing.
6. Increase distances to provide clearance for servicing.
Minimum Clearances
Figure 2
REMOVE CRATE
1. Remove all banding and pry off crate sides carefully so as not to damage the water heater.
2. Carefully roll/lift the water heater from the crate base.
MOVE WATER HEATER TO PERMANENT POSITION by sliding or walking. Place drain pan underneath water heater
INSTALL TEMPERATURE AND PRESSURE RELIEF VALVE (if not already installed).
This water heater must be located in an area where the general public does not have access to set temperatures.