Troubleshooting guide

13
Horizontal And Vertical Direct Vent Lengths
This Powered Direct Vent Gas Water Heater comes with one (1) direct vent kit. The venting system supplied with this
water heater is a coaxial (pipe within a pipe) design with the flue discharge tube on the inside and combustion air supply
on the outside. Optional direct vent components are available that can extend the horizontal length and/or vertical height
of the direct vent system to the maximum distances listed in the table below. This water heater must be installed using
the supplied or optional listed components without modifications. Reference the Venting Component Tables listed in the
Installation (Direct Vent System Installation) for the various system components.
Note: The supplied horizontal vent terminal may be used to vent through outside walls up to 24 in. (61 cm) thick.
Maximum Venting Distances (Horizontal, Vertical, or Combined)
Number of 90° Elbows Maximum distance of straight pipe (excluding vent terminal) to exterior wall
0 22 ft. 9 in. (7 m)
1 19 ft. 6 in. (6 m)
2 16 ft. 3 in. (5 m)
3 13 ft. (4 m)
Note: Each 45° elbow reduces the maximum venting distance by 19 1/2 in. (50 cm).
Direct Vent System Installation
Tools Required For Direct Vent Installation
The following minimum tools are required to properly install the direct vent system. Note: Wall construction will
determine tool usage.
Tape Measure
Drill
3/16 inch Diameter Drill Bit(s)
1/8 inch Diameter Drill Bit(s)
Masonry Drill Bit(s) (For Poured Concrete, Concrete Block and Brick Wall Construction)
Reciprocating Saw w/appropriate Blade(s) (Dependent on Wall Construction)
Chisel (For Poured Concrete, Concrete Block and Brick Wall Construction)
Hammer (For Poured Concrete, Concrete Block and Brick Wall Construction)
1/4 & 5/16 inch Nut Drivers (Preferred) or Slotted Head Screwdriver
Phillips Head Screwdriver
Materials:
Metal strapping to support vent piping.
IMPORTANT - Do not exceed the venting distances or the number of elbows listed above. Exceeding the
maximum venting distances may cause the water heater to malfunction or cause an unsafe condition.
NOTICE
The direct vent system must be properly installed. Failure to properly install the direct vent system could
result in property damage, personal injury or death.
Do not install any damaged direct vent system components. Contact the manufacturer of the water heater
for replacement parts.
The flow of combustion air must not be restricted. Keep the direct vent terminal openings clear of objects,
shrubs, snow and debris.
WARNING