Specifications

11
Installation (Venting) continued-
Vent pipes serving power vented appliances are classified by building codes as “vent
connectors”. Required clearances from combustible materials must be provided in
accordance with information in this manual under LOCATION OF WATER HEATER
and CLEARANCES, and with National Fuel Gas Code and local codes.
Part I - Venting Specifications for:
48 Gallon, 65,000 BTU input (189.3 L, 19.1 kW/Hr)
75 Gallon, 75,000 BTU input (283.9 L, 22.0 kW/Hr)
This water heater is a power vented appliance and is designed to vent its
products of combustion through 3” (7.6 cm) or 4” (10.2 cm) diameter Schedule 40
PVC pipe to the outdoors. This water heater may be either vented through the
wall or vertically through the roof. The blower outlet is designed to fit 3” (7.6 cm)
diameter PVC pipe. Use a 3” (7.6 cm) to 4” (10.2 cm) reducer to connect to the
vent outlet when using 4” (10.2 cm) PVC. Seal the joint between the PVC pipe
and the blower outlet collar with RTV sealant (See figure 2). Table 1 lists the
maximum vent lengths for this water heater using 3” (7.6 cm) PVC. If possible,
locate the water heater so that the venting length and number of elbows are kept
to the minimum distance necessary to reach the outside. If the installation
requires venting lengths that exceed the lengths listed for 3” (7.6 cm) PVC in
Table 1, then use 4” (10.2 cm) PVC for the vent connector. Table 2 lists the
venting distances allowed with 4” (10.2 cm) diameter PVC pipe. When venting
with 4” (10.2 cm) PVC, use a 4” (10.2 cm) to 3” (7.6 cm) reducer to exit through
the building wall with 3” (7.6 cm) PVC. Use 3” (7.6 cm) vent terminal supplied
with the water heater to terminate on the outside of the building. If the length of
the 3” (7.6 cm) PVC needed to go through the wall is greater than 14” (35.5 cm),
use 4” (10.2 cm) to go through the wall and reduce to 3” (7.6 cm) PVC
immediately after exiting the outside wall. Refer to the venting illustrations on the
following pages.
Make sure the vent pipe terminal elbow fitting is at least 1” (2.5 cm) away from
the edge of the wall.
TABLE 1 - VENT CONNECTOR LENGTHS
FOR 3” (7.6 cm) DIAMETER PVC
Terminating # of 90° Elbows
(excluding vent
terminal)
Maximum
Length
Minimum
Length
Through the Wall 1 40 ft (12 m) 2 ft (.6 m)
Through the Wall 2 35 ft (10.5 m) 3 ft (.9 m)
Through the Wall 3 30 ft (9 m) 5 ft (1.5 m)
Through the Wall 4 25 ft (7.5 m) 8 ft (2.4 m)
Through the Roof 1 40 ft (12 m) 2 ft (.6 m)
Through the Roof 2 35 ft (10.5 m) 3 ft (.9 m)
Through the Roof 3 30 ft (9 m) 5 ft (1.5 m)
Through the Roof 4 25 ft (7.5 m) 8 ft (2.4 m)