Service Manual

10
10
Sequence of Operation
Lockout Conditions
The system will go into lock out mode for the following reasons:
1. Error Code 110 (Ignition failure occurred)
a. Control board will go into “Soft Lockout” if the main burner cannot be lit or fails to prove flame
after 3 ignition trials. The water heater display indicates a lockout condition by showing an error
code number 110 with “Service Needed” in the control display window. Refer to error codes in
the diagnostic section of this Service Manual. In a Soft Lockout condition, the control will wait for
15 minutes and then make 3 more attempts to light the main burners. Soft lockout reset is
accomplished by depressing the lower right button under “Reset” for 3 seconds.
2. Error Code 80 (High limit overheat condition)
a. If the top of the tank should exceed 207°F (92.7°C), then the high limit control will shut off the
burner and the water heater will go into a “Hard Lockout.” Error code 80 will be shown in the
water heater display. The control can only be reset in the Service Mode, which is detailed in the
Troubleshooting section (page 13).
3. Error Code 67 (ILK off)
a. If the vent safety switch located on the draft hood should open, the gas valve will close, the
blower will post-purge and error code 67 will appear on the display. The lockout condition will
reset once the problem is corrected and the switch reset. Refer to Vent Safety Switch Testing
and Replacement.
Connection/Wiring Diagram