Data Sheet
Table Of Contents
- 1. General Technical Data
- 2. Product versions
- 3. Control functions
- 4. Approvals
- 5. Materials
- 6. Dimensions
- 7. Performance specifications
- 7.1. Fluidic data
- Overview of fluidic data for flow below seat (for gases, steam and liquids)
- Pilot pressure diagram with flow direction below seat (control function B, seat seal PTFE)
- Overview of fluidic data with flow above seat (for gases and steam)
- Pilot pressure diagram with flow direction above seat (control function A, seat seal PTFE)
- 7.2. Operating limits
- 7.1. Fluidic data
- 8. Product accessories
- 9. Networking and combination with other Bürkert products
- 10. Ordering information
Type 2000
5 | 26
Visit product website
3. Control functions
CAUTION
Riskofdamageduetoburstingpipesandburstingequipmentwhentheowisabovetheseat.
In the case of liquid mediums, water hammer can occur causing pipes and the device to burst.
Do not use valves with ow above the seat for liquid mediums..
Control function (CF) Description
Flow direction below seat for liquids, steam and gases
2 (P)
1 (A)
CF:A,pneumaticallyoperatedon/ovalve
2/2way
Flow direction below seat
Normally closed by spring force
2 (P)
1 (B)
CF:B,pneumaticallyoperatedon/ovalve
2/2way
Flow direction below seat
Normally open by spring force
Flow direction above seat for steam and gases
2 (A)
1 (P)
CF:A,pneumaticallyoperatedon/ovalve
2/2way
Flow direction above seat
Normally closed by spring force
4. Approvals
Approvals Description
Food contact
Materials in contact with the medium conform to EC Regulation 1935/2004 (option)
Materials in contact with the medium conform to FDA (option)
Drinking water
Suitable for use with drinking water with medium temperature up to 85 °C according to KTW, W270
(option)
Oxygen
Suitable for use with gaseous oxygen with medium temperature up to 60 °C and operating pressure up to
20bar(g) (option)
Explosion proof
As category 2 device suitable for zone 1/21 and zone 2/22 (option)
ATEX:
II 2G Ex h IIC T4 Gb
II 2D Ex h IIIC T135 °C Db
IECEx:
Ex h IIC T4 Gb
Ex h IIIC T135 °C Db
Fuel gases
Approval according to the European Gas Appliance Regulation (EU) 2016/426, DVGW DIN EN 161 and
DIN EN 16678, Class A or Class D, suitable for medium temperature 0…60 °C,
ambient temperature - 10…140 °C and operating pressure 0…16bar(g) (option)
Safety requirements
Evaluation of functional safety according to IEC 61508 (on request)