7. Product accessories
7.1. Accessoriescapacitivebuermodule
Note:
• Dimensions see “3.2.Capacitivebuermodule”onpage6.
• Ordering information see “8.4. Ordering chart accessories” on page 12.
Accessories Description
Motor valve(s) connection
24 V DC power supply
For example: Single phase,
primary switched mode power
supply Type 1573
• Capacitive buer module for moving to a safety position in case of power failure
• In order to be able to move to a safety position of the valve in the event of a power failure, the
valve must be supplied with voltage via the capacitive buer module. In the event of a power
failure, the buer module provides an output voltage of 18V DC for a few seconds. The re-
duced input voltage is detected by the valve and the safety position is approached according-
ly. Up to 3 valves of Type 3280 or 2 valves of Type 3285 can be connected to a buer module.
Factory setting of the safety position: “valve closed”
• For standard version (functionality available as of software version A.08): adjustable via DIP
switches (for the reverse operating direction, the safety position changes to “valve open”.
• For positioner and process controller version (functionality available as of software version
A.06): adjustable via Bürkert Communicator (user-dened safety position)
7.2. Software Bürkert Communicator
Note:
To install the software, click here.
An adjustment of the valve by the Bürkert Communicator is only possible with the positioner or process controller versions.
Part of Bürkert’s new EDIP program (Ecient Device Integration Platform) is the Bürkert Communicator. This software can be run un-
der MS-Windows and it is available on Bürkert’s website for free. The Bürkert Communicator allows convenient system conguration
and parametrisation of all connected eld devices. An accessory part, the büS stick serves as the interface between computer and
process instruments (see “8.4. Ordering chart accessories” on page 12) The Communicator allows:
• Diagnostics
• Parameterisation
• Registration and storage of process data
• To watch graph of process
• To update rmware of the device connected
• Parameterisation of the integral positioner and (if available) process controller