Data Sheet

Type 3285
4 | 14
Visit product website
1.2. Standard, positioner and process controller version
Technical data Device variant
Standard Positioner Process controller
ON/OFF Control valve Analogue Digital(eldbus) Analogue Digital(eldbus)
Electrical
connection
M12 Plug,
A-coded, 8pin
M12 Plug,
A-coded, 8pin
M12 Plug,
A-coded, 8pin
M12 Plug,
A-coded, 5pin
M12 Plug,
A-coded, 8pin
and
M12 Socket,
A-coded, 5pin
M12 Plug,
A-coded, 5pin
and
M12 Socket,
A-coded, 5pin
Input signal
(setpoint)
Digital input:
0…5V
(log. 0, valve
closed) or
10…30V
(log. 1, valve
open)
4…20mA,
0…10V,
or
PWM (800Hz)
4…20mA,
0..20mA,
0…10V,
or
0…5V
4…20mA,
0..20mA,
0…10V,
or
0…5V
Input signal
(actual value
from ext.
Sensor)
4…20mA,
0..20mA,
0…10V,
0…5V
4…20mA,
0..20mA,
0…10V,
0…5V,
or
Frequency
(5…2000Hz)
Input imped-
ance for ana-
logue input
22 kΩ 60 Ω (current),
22 kΩ (voltage)
60 Ω (current),
22 kΩ (voltage)
60 Ω (current),
22 kΩ (voltage)
60 Ω (current),
22 kΩ (voltage)
Output signal
(actual value)
Digital output:
PNP, max.
100mA
current lim-
its, feedback
function (output
signal
active, when
valve closed)
Digital output:
PNP, max.
100mA
current lim-
its, feedback
function (output
signal
active, when
valve closed)
0/4…20mA
(max. load: 560
Ω),
0…5/10V
(max. current:
10mA)
0/4…20mA
(max. load: 560
Ω),
0…5/10V
(max. current:
10mA)
Fieldbus
interface
büS / CANopen büS / CANopen
Parameteriza-
tion Tool
Bürkert
Communicator
(Connection via
büS stick)
Bürkert
Communicator
(Connection via
büS stick)
Bürkert
Communicator
(Connection via
büS stick)
Bürkert
Communicator
(Connection via
büS stick)
2. Materials
2.1. Chemical Resistance Chart – Bürkert resistApp
Bürkert resistApp – Chemical Resistance Chart
You want to ensure the reliability and durability of the materials in your individual
application case? Verify your combination of media and materials on our website or in
our resistApp.
Start Chemical Resistance Check