6. INSTALLATION
6.1. Safety instructions
DANGER!
Risk of injury from high pressure in the equipment/device.
Before working on equipment or device, switch off the pressure and
deaerate/drain lines.
Risk of electric shock.
Before working on equipment or device, switch off the power supply
and secure to prevent reactivation.
Observe applicable accident prevention and safety regulations for
electrical equipment.
Risk of injury from improper installation.
Installation may be carried out by authorized technicians only and
with the appropriate tools!
Secure system from unintentional activation.
Following installation, ensure a controlled restart.
6.2. Fluid installation
DANGER!
Risk of injury from high pressure in the equipment/device.
Before working on equipment or device, switch off the pressure and
deaerate/drain lines.
Installation position: any, coil preferably upwards.
Procedure:
Before installation, clean any possible dirt off the pipelines and flange
connections.
If required, install a dirt trap to prevent malfunctions.
Mesh size:
0,2 – 0,4 mm
Pay attention to the flow direction of the valve.
from 1(P) 2(A) (Circuit function C) or
from 1(P) 2(B) (Circuit function D)
english
9
Valve with threaded connection:
Use PTFE tape as sealing material.
NOTE!
Caution risk of breakage.
Do not use the coil as a lifting arm.
Hold the device with a suitable tool (open-
end wrench) on the body and screw into
the pipeline.
Valve with flanged connection:
Remove the cover plate.
Loosen the nut on the coil and remove coil.
Seal
Nut
Coil
Cover plate
Manifold
Fig. 2: Valve with flanged connection
WARNING!
Risk of injury due to escaping medium.
Make certain the seals included with delivery are properly seated in
the valve.
Ensure that the manifold is even.
Ensure that the surface quality of the manifold is adequate.
Insert the seal into the body.
Screw the body onto the manifold (tightening torque: max. 1.5 Nm).
Attach the coil and screw on the nut (tightening torque: max. 5 Nm).
english
10
6.3. Electrical connection with cable plug
DANGER!
Risk of electric shock.
Before working on equipment or device, switch off the power supply
and secure to prevent reactivation.
Observe applicable accident prevention and safety regulations for
electrical equipment.
If the protective conductor contact between the coil and body is
missing, there is danger of electrical shock.
Always connect protective conductor.
Check electrical continuity between coil and body.
Seal
max. 1 Nm
Type 2508
Fig. 3: Electrical connection with cable plug
Note the voltage and current type as specified on the type label.
Check that seal is fitted correctly.
Connect and tighten the cable plug (tightening torque: max. 1 Nm).
The cable plug can be turned by 4 x 90°.
Control of pulse version
Correct polarity is essential to ensure that the device functions:
Note identification on the upper side of the coil.
Pulse duration at least 50 ms.
switch ON +
+ switch OFF
Terminal 1
Terminal 2
Protective conductor connection
Fig. 4: Pulse version