User guide

20
Technical data
Type 8025 / 8035
6.6. Specifications of the connected flow sensor
Sensor input
signal frequency
pulse signal (Hall)
sinus signal (coil)
2,5 to 400 Hz
NPN, open collector
typical sensitivity of 35 mV peak-peak, at 252 Hz
Sensor output
power supply 10-34 V DC (V+ minus 2 V DC), 1 mA max.
6.7. Electrical connection
Version Connection features
With male fixed
connector
Female connector (type 2508 supplied)
For the female connector type 2508 with order code 438811 and the female connector type 2509
(not supplied) with order code 162673, use a shielded cable.
external diameter of the cable: 5 to 8 mm
cross section of the wires: 0.2 to 1.5 mm
2
max. length of the power supply, current output and pulse output connection cables: 50 m
With terminal strip,
with or without cable
glands
Shielded cable (not supplied):
external diameter of the cable: 6 to 12 mm (4 to 6 mm when using a multiway seal)
cross section of the wires: 0.2 to 1.5 mm
2
All Cross section of the local earthing wire: 0.75 mm
2
English