User guide
46
operating and commissioning
Type 8025 / 8035
9. OPERATING AND COMMISSIONING
9.1. Safety instructions
WARNING
Risk of injury due to nonconforming operating.
Non-conforming operating could lead to injuries and damage the device and its surroundings.
• The operators in charge of operating must have read and understood the contents of this manual.
• In particular, observe the safety recommendations and intended use.
• The device/installation must only be operated by suitably trained staff.
WARNING
Danger due to non-conforming commissioning.
Non-conforming commissioning could lead to injuries and damage the device and its surroundings.
• Before commissioning, make sure that the staff in charge have read and fully understood the contents of the manual.
• In particular, observe the safety recommendations and intended use.
• The device / the installation must only be commissioned by suitably trained staff.
• Before commissioning, set the K Factor of the fitting used. See chap. "9.6.3".
9.2. Operating levels of the device
The device has two operating levels: the Process level and the Configuration level.
The Process level makes it possible:
• to read the flow rate measured by the device, the value of the current transmitted on the 4-20 mA analogue output, the
values of both the daily and main totalizers;
• to reset the daily totalizer;
• to access the Configuration level.
The Configuration level has two menus (Parameters, Test) and makes it possible:
• to set the device parameters;
• to test some device settings.
Tab. 6: Default settings of the device
Function Default value
LANGUAGE English
UNIT of the flow rate L/min, 1 decimal
UNIT of the totalizers L
Number of decimal positions 1
4 mA current output 0.000
20 mA current output 100.0
K FACTOR
51.20
FILTER
5
Value of a pulse (PU)
00.05
Unit of the pulse output
L
Relay 1- 40.0
Relay 1+ 50.0
Relay 1 inverted no
Relay 2- 80.0
Relay 2+ 90.0
Relay 2 inverted no
English